Design Precision
At Enerset Power Solutions, we provide power transformers with unique requirements that must be met with precision. Let our experienced professionals help with an innovative, competitively-priced solution to meet your specific needs.
For the design and manufacturing of our transformers, a 3D modeling is used to fully integrate all parts and components in a virtual basis and facilitate the assembly process. HiB grade silicon steel is used to deliver high efficiency in a compact design. Our transformers are designed to protect against environmental hazards. Our distribution and pad-mounted transformers are available in live-front or dead-front designs and radial or loop feed configurations.
- FEATURES
- SPECIFICATIONS
Operating voltages for 300 kVA through 1500 kVA rating
High Voltages (MV)
- Various dual high voltages
- 2400 through 34500 V Delta
- 4160Grd Y/2400 V through 34500 Grd Y/19920 V
High Voltage Taps
- All voltages are available with 5 or 7 step taps
- Dual voltage taps provided only on the higher voltage
Low Voltages (LV)
- 208Y/120 V, 480Y/277 V, 480 V, 240 V‚ and 240 V‚ with 120 V mid-tap in one phase
- 4160Y/2400 V, 4160 V, 2400 V
Primary Insulation Classes
- 35 kV, 200 kV BIL and below
Operating voltages for 2000 kVA through 7500 kVA rating
High Voltages (HV)
- 12470Grd Y/7200 V through 34500 Grd Y/19920 V
- 4160 V through 34500 V Delta
- Various dual high voltages
Voltage Taps
- All voltages are available with 5 or 7 step taps
- Dual voltage taps provided only on the higher voltage
Low Voltages (LV)
- 480Y/277 V, 480 V , 240 V – 4160Y/2400 V, 4160 V , 2400 V
Impedance Guidelines
- 300 kVA – 500 kVA : 2.8 – 5.0% nominal
- 750 kVA – 2500 kVA : 5.75% nominal
- 3000 kVA – 7500 kVA : Consult Enerset Power Solutions
- High efficiency design – TP1
- Special ambient design
- Low sound level design
- 50 Hz and 60 Hz design
- K-factor rating
- Network type transformers
- Maximum voltage and MVA – Up to 138 kV and 100 MVA
- Off Load (NLTC) and On Load tap Changer (OLTC) are available.
- Available fluids – Mineral oil, silicon oil and FR3 (vegetable oil)
- Standards – ANSI, IEEE, NEMA and IEC
- 65°C average winding rise
- Unique step-stacked core and rectangular wound core
- 60 Hz standard, optional 50 Hz
- Mineral oil, optional FR3
- Standards – ANSI, NEMA, IEEE65°C average winding rise